The CMS of TIG mainly aims to increase battery utilization, prevent battery overcharge and overdischarge, prolong service life of batteries, and monitor battery status.

| Electrical performance | minimum value | Typical value | Maximum value | |
|---|---|---|---|---|
| Environment | Operating temperature (℃) | -40 | 65 | |
| Storage temperature (℃) | -40 | 85 | ||
| Relative humidity (%) | 5 | 95 | ||
| Atmospheric pressure (kPa) | 86 | 106 | ||
| Power supply | Voltage range (V) | 16 | 24 | 32 |
| Operating power (W) | 5 | 10 | ||
| Protection against reverse power connection | Support | |||
| Voltage detection | Channel number | 2 | ||
| Detection range (A) | 50 | 1000 | ||
| Detection precision (%) | ±5 | |||
| Current detection | Channel number | 1 | ||
| Detection range (A) | -FSR | -FSR | ||
| Power supply of current sensor (V) | ±15 | |||
| Detection precision (%) | ±1 | ±1.5 | ||
| Insulation | Applicable voltage range (V) | 100 | 1000 | |
| detection | Detection precision (%) | ±10 | ||
| Communication interface | Number of CAN interfaces | 3 | ||
| Number of RS485 interfaces | 1 | |||
| Number of RS232 interfaces | 1 | |||
| Other interfaces | Digital signal input ports | 6 | ||
| Switch control output ports | 8 | |||
| Standby analog input ports | 2 | |||